It's Wednesday. This July, a routine transmission fault in Northern Virginia made 3,800 MW of demand vanish in an instant. The grid's rulebook is now catching up with its biggest new customers.

In today's edition:

๐Ÿ”Œ Big Story: NERC's data center rules

โšก Quick Hits: Britain zones its reserve markets, TRISO fuel licensing, California geothermal drilling money, MHI on off-grid costs, Helion's new date

๐Ÿ’ฐ Capital: Energy Vault's $78M merchant battery, energy stocks ride the Nvidia drama

๐Ÿ“‹ Policy Watch: PJM's 12-month queue, Ohio's off-grid gas plant, Duke's Carolinas plan

๐Ÿ“Š Chart of the Day: US batteries keep setting records

The Big Story
NERC tells big data centers to disclose how they swing

NERC adopted its first reliability standards for computational loads in October, and IEEE Spectrum reports they would require facilities with at least 50 MW of computing load connected at 100 kV or above to share detailed models of their power draw and fault response, including tripping settings, if FERC approves them. Sites would also send real-time operating data, follow grid operators' instructions to cut or hold demand and install disturbance recorders.

โ

We need information from these data centers to be able to model and study them.

โ€” Latrice Harkness, Director of Engineering, NERC
  • On July 22, Northern Virginia data centers drawing 3,800 MW disconnected after a routine line fault and switched to backup power, sending frequency and voltage spikes across the system.

  • A draft NERC report cited by IEEE Spectrum counts at least eight cases since 2022 in which data centers abruptly shed 200 to 1,800 MW after grid faults.

  • A 2025 NERC white paper documented one data center section ramping from 6 MW to 30 MW in a quarter-second.

  • Ride-through limits are on NERC's roadmap but are not yet rules; NERC plans to set criteria against forced oscillations next year.

Quick Hits
Technology milestones from across the grid

Zones, fuel pebbles, hot rocks, turbine math, and a fusion date that moved.

  • NESO proposed splitting Great Britain into 12 zones for its Dynamic Response and Reserve markets, so prices could differ by location, adding site-specific upside and risk for batteries. ESS News

  • Standard Nuclear has documented safety analyses for TRISO fuel plants in Tennessee and Idaho under DOE review, a step toward filling 2027 fuel orders. World Nuclear News

  • The California Energy Commission expects to open an $18 million geothermal exploration and drilling solicitation in January 2027, split across three to four awards. ThinkGeoEnergy

  • Mitsubishi Heavy Industries CEO Eisaku Ito said the cost of off-grid power will push data centers back toward utilities and that a load shortfall would have a "limited" effect on turbine orders. Utility Dive

  • Helion now targets full power at its first 50 MW fusion plant by the end of 2030, later than its earlier 2028 goal, Heatmap reported. Heatmap

The Capital Stack
Energy Vault closes $78 million for a merchant Texas battery

Energy Vault closed $78 million in non-recourse construction and bridge debt for SOSA, a 150 MW/300 MWh merchant battery in ERCOT, ESS News reported. It is the first project financed under the company's Asset Vault ownership platform, with commercial operation targeted for the third quarter of 2027.

Source: ESS News

Also in the capital stack:

Bloom Energy, GE Vernova and Constellation jumped more than 18%, more than 8% and 6% as Jensen Huang returned to Nvidia, with power equities still trading on AI sentiment. Latitude Media

Loving today's brief? Forward it to your team. And reply back with news we should include tomorrow.

Policy Watch

  • PJM proposed a 12-month annual interconnection cycle for generators and large loads, replacing 18- to 24-month studies with a 4-month screen, a 7-month impact study and a month for contracts; applications would open toward the end of 2027 if FERC approves, Heatmap reported. Heatmap

  • The Ohio Power Siting Board approved an 800 MW gas plant in Ashville that will serve an EdgeConneX data center without connecting to the grid, despite 81% local voter opposition. Off-grid supply for data centers now has a state siting precedent. Canary Media

  • North Carolina regulators advanced Duke Energy's Carolinas resource plan, targeting 8.1 GW of solar and 5.4 GW of storage by 2034 alongside 2,720 MW of combined-cycle gas. Storage now sits at the center of the Southeast's biggest utility plan. T&D World

Chart of the Day
US battery installs run 20% ahead of last year

SEIA/BMI US battery deployments chart, via Canary Media

The US installed 20% more battery storage in the first nine months of 2026 than a year earlier, and 11 states have already set annual records. SEIA and Benchmark Mineral Intelligence expect full-year additions to beat 2025 by 26%, even as residential installs fall 8%.

Source: Canary Media ยท Nov. 20, 2026

Like our newsletter?

Or forward this link: {{rp_refer_url}}

You currently have {{rp_num_referrals}} referrals. We're building out rewards for our most active subscribers, including merch and exclusive content!

Who We Follow
And you should too!

Mavka Report

Mavka Report

Mavka Report is a weekly newsletter digest bringing you the latest global news on capital raises and M&As across six sectors of coverage: physical AI, data center infrastructure & IT services, smar...

Sunya Scoop

Sunya Scoop

Get smarter about energy.

How Did You Like Today's Brief?

Login or Subscribe to participate

Loved it? Forward it.

And reply back with some news and stories we should include tomorrow!